Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, 508 & 750) Installation User Manual
Page 21

2
Page
2 - 2
TANK SENTINEL
®
INSTALLATION GUIDE
TABLE 2-1.
STANDARD (STD) TANK SENTINEL PROBES
dimensions are listed in inches (mm)
Probe
Probe
Maximum
Model TSP-LL2
Model
Shaft
Tank
Probe
Length
Diameter
Overall Length
LL2-29
29(737)
24(610)
39(991)
LL2-41
41(1041)
36(914)
51(1295)
LL2-53
53(1346)
48(1219)
63(1600)
LL2-69
69(1753)
64(1626)
79(2007)
LL2-77
77(1956)
72(1829)
87(2210)
LL2-81
81(2057)
76(1930)
91(2311)
LL2-89
89(2261)
84(2134)
99(2515)
LL2-101
101(2565)
96(2438)
111(2819)
LL2-113
113(2870)
108(2743)
123(3124)
LL2-125
125(3175)
120(3048)
135(3429)
LL2-131
131(3327)
126(3200)
141(3581)
LL2-137
137(3480)
132(3353)
147(3734)
LL2-149
149(3785)
144(3658)
159(4039)
Riser Pipe Length Calculations
Minimum Riser Length
Start with the overall length of the probe, add 5 inches (127mm) for the support
chain, and subtract the tank diameter. See Example minimum riser length
calculations (below) for a TSP-LL2-101 probe in two different sized tanks.
92 Inch (2337mm)Tank
96 Inch(2438mm) Tank
inches (mm)
inches (mm)
TSP-LL2-101 Probe Overall Length
111(2819)
111(2819)
Allowance for suspension chain
+
5(127)
+
5(127)
Total
116(2946)
116(2946)
Tank diameter
– 92(2337)
– 96(2438)
Minimum Riser Length
= 24(609)
20(508)
It is possible through the minimum riser length equation for the calculation to be
less than 18 inches. It is recommended that the riser be at least 18 inches (457
mm) for a model TSP-LL2 Probe (Reference Figure 2-1).
NOTE