Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, 508 & 750) Installation User Manual
Page 12
INSTALLATION OVERVIEW
Page
1 - 7
1
The risk of loss or damage to merchandise in shipping remains with the buyer. It is
the buyer’s responsibility to file and settle the claim with the carrier.
You must obtain a Return Material Authorization (RMA) number before returning
any equipment to INCON. See INCON Warranty Policy P/N 000-1197 about the
RMA procedure requirements. Shipments of returned material which have not
been authorized will be returned freight-collect.
Please have a pen and a piece of paper at hand when you call INCON – Technical
Service Department,1-800-984-6266 (+207 283 0156), for a Return Material
Authorization number. One of our Service Technicians will also give you the return
shipping address and shipping instructions.
Return Shipping Charges
Under Warranty
INCON will pay all freight and insurance charges for all “Under-Warranty” RMA’s.
Non-Warranty
It is the buyer’s responsibility to prepay all freight and insurance charges for Non-
Warranty RMA’s.
Reference chapter 10 in this manual for Warranty issues.
Materials Required for this Installation
TABLE 1-1: Cables Required for Liquid Level Probes
The type of cable required for Liquid Level Probes is based on the length of
cable run from the probe to the Tank Sentinel console.
Cable Type
Probe Model: TSP-LL2
Belden No.
87760 0.12” (3 mm) OD ...............
260
ft (80 M) maximum
*
Belden No. 87761 0.12” (3 mm) OD ..............
400
ft (122 M) maximum
Belden No.
88761 0.12” (3 mm) OD ..............
400
ft (122 M) maximum
*
Belden No. 89182 0.31” (7.9 mm)OD ...........
1500
ft (450 M) maximum
Only use cable specified above – DO NOT exceed maximum
cable lengths. See probe label / shipping tube for Model, S/N, Gradient, etc.
*
You can order this cable from INCON
Intrinsically safe (I.S.) probe cable(s) and leak detection
sensor wires/cables may be run together within the same
conduit.
NOTE
NOTE