Installing TSP-LL2 Probe Floats

1) Remove the stainless steel e-clip, and washer / spacer (this is the float retainer

assembly)

2) For Chemical probes, install the stainless steel TSP-K4AS riser cap adapter by

tightening the lower swagelock fitting (see Figure 6.2).

3) Slide the product float onto the probe shaft with the white-colored stem facing up,

toward the probe head (or the 2 inch (51 mm) float without ballast, or the TSP-SSP
float)

4) Next, install the water (interface) float on the probe shaft in a similar manner (N/A

for the Chemical Probe – TSP-LL2-C__)

5) Install the water interface float. Make sure that the water float you are installing is

appropriate for the liquid that is stored in the tank. The standard water float used
with gasoline has a red-colored stem. The 2 inch (51 mm) float for gasoline has a
G stamped on the nickel plated ballast. The water float used with fuel oils and
diesel fuel has a blue-colored stem. The 2 inch (51 mm) float for diesel or fuel oils
has a D stamped on the nickel plated ballast).

6) Reinstall the float retainer assembly (Stainless Steel washer/spacer, and the E-

Ring clip) on the end of the TSP-LL2 probe shaft. Floats will be lost if these parts
are not properly installed.

Figure 6-1

TSP-LL2 Standard Probe Riser Cap Adapter (TSP-K4A)

1

5

6

PROBE CABLE

* CABLE ROUTED THRU

COMPRESSION GLAND

(CORD GRIP) FITTING

* CORK GASKET

* RISER CAP

ADAPTER

TSP-K4A PROBE INSTALLATION KIT DETAIL

* EYE BOLT THRU SHOULDER
WASHER (INSULATION SIDE UP).
USE THE WING NUT TO ADJUST
PROBE HEIGHT

3

2

* RINGS & SUPPORT CHAIN
( CUT CHAIN TO THE EXACT
LENGTH REQUIRED. DO NOT
LEAVE SURPLUS CHAIN
ATTACHED ! )

* TSP-K4A
RISER CAP

7

* STEEL SUPPORT PLATE (WITH
RUBBER CABLE GROMMET AND
SHOULDER WASHER
(INSULATION SIDE UP).

4

4 INCH DIA. RISER PIPE

ANSI SCH 40 M M 8 NPT

DN115 BSP 4-11

PROBE MODEL #, SERIAL #,

GRADIENT VALUE,

MAX TANK SIZE, LENGTH, &

RTD - TEMP SENSOR LOCATIONS

ON PROBE HEAD LABEL