1

Page

1 - 14

TANK SENTINEL

®

INSTALLATION GUIDE

Step 8

With power off:

Install conduit and connect the line power to the console. Leave

the line power Circuit Breaker off at the electrical power panel until all wiring has
been verified correct.

Step 9

Install a separate telephone line for the optional modem / fax.

Step 10 With power off:

Install optional accessories, conduit, and wiring to external

devices, such as discrete/run inputs or line leak detectors, as detailed in this
manual or in an installation addendum.

Step 11 With power off:

Install optional conduits and wire external alarm devices, such as

a TS-RK (remote Alarm Acknowledge unit) and TS-RA1 or TS-RA2 (remote Tank
Overfill Alarm unit) as described in their Installation manual.

Step 12 Review and verify that all level probe wiring is completed in accordance with this

manual, and that all other devices (Sensors, External Devices, and Alarm units,
etc.) are wired correctly. Incorrect liquid-level probe wiring, or leak-detection sensor
wiring, will damage the console at start-up.

Step 13 Reinstall all terminal safety shields/covers. Power up and program the Tank

Sentinel

®

system for your application, as described in the Programming Guide.

Step 14 Test and then install each of the level probes in their tanks.

Step 15 Test and then install the leak detection sensors between the walls of the double

wall tanks, in liquid sumps, or other locations as described in their installation
manual ...an installation manual is provided with each type of sensor.

Step 16 Seal all tested probe and sensor EYS conduit fittings with epoxy and then reinstall

all junction box cover gaskets and covers.

❖ —