beautypg.com

Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, 508 & 750) Installation User Manual

Page 38

background image

6

Page

6 - 4

TANK SENTINEL

®

INSTALLATION GUIDE

Recording RTD/Temperature Sensor Locations

RTD/Temperature sensors measure the temperature of the product. The Tank
Sentinel uses the number and position of these temperature sensors within each
probe for precise volumetric calculations.

For “special” length probes that are not listed in TABLE 2.1:

accurately

record the RTD/Temperature Sensor Locations in this section. Skip this step if
you are not installing a special length probe.

Sensor number 1 is always at the bottom of the probe shaft, which will be the
smallest number listed on the Serial No./Model No. label at the probe head. INCON
probes have 5 temperature sensors (standard), but up to 6 are possible.

This information is required to program the console to work with a “special” length
probe (one that is not listed in TABLE 2.1 of this manual), or with a probe that has
6 RTDs.

Locations are not required when

TSP-LL2-__I inventory only probes are used.

RTD/Temperature Sensor Locations for Special Probes

RTD #

– Probe 1

RTD #

– Probe 2

6

6

5

5

4

4

3

3

2

2

1

1

RTD #

– Probe 3

RTD #

– Probe 4

6

6

5

5

4

4

3

3

2

2

1

1

NOTE

NOTE

NOTE