SYSTEM WIRING

Page

7 - 35

7

After all System Wiring is Complete — Steps

1) Check that all wiring is accurately terminated.

2) Check that each wire is held securely by the terminal hold-down screw (pull

slightly on each wire to check this). If wiring is loose or terminated improperly,
remove the wire, unscrew the terminal hold-down screw (completely) and
re-terminate.

3) Reinstall the metal I.S. cover over the Intrinsically Safe probe / sensor interface

terminals.

4) Reinstall the clear safety shield/covers over the Tank Sentinel AC power/Alarm

Relay/Input terminals.

5) Reinstall the covers over the optional BriteBox

®

modules.

WARNING

Failure to replace the safety covers and shields will result in a

dangerous situation. An explosion hazard, or an electrical shock hazard will be
created, which may result in property damage, injury, or loss of life.

❖ —