background image

I N T E L L I G E N T C O N T R O L S I N C

h t t p : / / w w w . i n t e l c o n . c o m

7 4 I N D U S T R I A L P A R K R D S A C O M E 0 4 0 7 2

U

S

A

Replacement Parts Instructions

0000232.DOC

E - m a i l :

t e c h @ i n t e l c o n . c o m

F A X 1 - 2 0 7 - 2 8 2 - 9 0 0 2

T E L 1 - 8 0 0 - 9 8 4 - 6 2 6 6

P A G E

1 o f 1

s a l e s @ i n t e l c o n . c o m

F A X 1 - 2 0 7 - 2 8 3 - 0 1 5 8 T E L 1 - 8 0 0 - 8 7 2 - 3 4 5 5

Bottom & Side Views

LSU Screen

LSU Leak Sensing
Flow Tube
(outlet at bottom)

LSU O-Ring

Changing the TS-LLD LSU Filter Screen or O-Ring

Parts Required:

1.

TS-LLD Installation Manual
(INCON P/N 000-1359)

2.

TS-LLD LSU Stainless Steel Filter Screen

3.

and/or TS-LLD LSU O-Ring

Tools & Material Required:

1.

Manufacturers’ documentation for the Submerged Turbine Pump (STP)

2.

See the Installation Manual for a detailed list of Materials & Tools Required

Old TS-LLD LSU – Removal Steps:

1.

DANGER

disconnect

electrical power as described in the LSU Installation and

Safety chapters of the TS-LLD Installation Manual.

2.

Bleed / relieve the pipe line pressure !

3.

Follow the LSU Installation steps shown in the TS-LLD Installation Manual – IN
REVERSE ORDER –
to remove the LSU.

Filter Screen – Installation:

1.

Remove the old Filter Screen and / or O-ring

2.

See the LLD Maintenance & Service chapter in the TS-LLD Installation Manual
for inspection issues too. Install the new Filter Screen while being careful not to
spread the screen apart too much (it is soft and easy to deform). A new O-ring
can be installed by stretching out enough to fit on the LSU until it can seat in the
O-Ring groove (do not roll or twist the O-Ring).

3.

Reinstall the LSU

. Follow the Safety Instructions, the steps for LSU

Installation, and the After Installation Steps / Testing (as detailed in the
Installation Manual).

Need Help: