Memory Backup Battery Replacement Instructions
for Tank Sentinel, AutoStik, & BulkStik ATGs
Parts & Materials
Required:
One new 3 volt lithium
battery (INCON P/N:
TSSP-BAT / 390-0004), a
thin piece of adhesive tape,
and a digital multimeter with
test probes.
Diagram:
Testing the
Battery ( B1 )
Use a digital multimeter set
to read 5 DC volts and
measure the DC voltage
between the + battery
terminal and – ground or
the yellow-colored metal
shield
(+2.8 to +3.3 volts DC is good).
When to Test the
Battery Voltage (Schedule)
: Yearly after the first two years of operation or use.
DANGER Electrical Shock Hazard.
Make sure all safety shields are installed to
prevent electrical shocks — DO NOT touch any device other than the battery.
Removal & Installation Steps
( with Tank Gauge Power ON & SW 1 ON ):
1.) Printout the complete system and tank setup reports for all tanks. (
Note
– if the
power goes out or is turned off while the battery is out of its holder then all of the
setup/programmed values of the system will be lost. If this happens then the entire
tank gauge will have to be reprogrammed ).
WEDGE UP HERE
ABOUT 1/8 INCH
Battery Cutaway
Side View
b
PRY OUT HERE
a
Yellow
colored
metal
shield
b
TS-1001/N-N U10
VER No. DATE
a
Replace the battery if the voltage reading is below
2.8 volts DC