Line power wiring, Page 7 - 4 tank sentinel, Installation guide – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, 508 & 750) Installation User Manual

Page 47

background image

7

Page

7 - 4

TANK SENTINEL

®

INSTALLATION GUIDE

Figure 7-2b.

Basic TS-2001 Console Internal View / Component Location

Line Power Wiring

At the Electrical Power panel, use or install a 10 amp circuit breaker — this
breaker should be dedicated to supply power only to the Tank Sentinel system.
Mark this circuit “Tank Sentinel System [power] - ONLY” on the circuit label (at
the back of the Electrical Power Panel door). Reference Figure 7-3a or 7-3b
and the wire connection list above it for line power wiring.

CAUTION

Avoid connecting other equipment to this circuit. Faulty system

operation can result from electrical noise created if other equipment is
connected to this dedicated circuit.

ELECTRICAL DANGER

Make sure the Tank Sentinel Power circuit

breaker is turned off during any installation. Lethal voltages are present inside
the console which could kill or injure you. Also, secure the Tank Sentinel circuit
breaker (C.B.) in the off position, and attach a “lockout”, which is dated and
signed by you, to prevent accidental closure, injury, or death.

ELECTRICAL DANGER

The ground bus in the electrical panel must be

connected to earth ground as required by the National Electrical Code (or
Canadian Electrical Code if applicable). If the ground bus is not properly
connected to earth ground, or if the I.S. Safety Ground is not properly

TS-1001/N-N U10
VER No. DATE

WARNING:

LETHAL VOLTAGES COULD EXIST !

LOCATE AND DISCONNECT ALL EXTERNAL POWER SOURCES

BEFORE WORKING ON OR SERVICING THESE CIRCUITS —
REINSTALL THIS COVER BEFORE OPERATING EQUIPMENT.

W

ARNING

THIS COVER MUST BE INST

ALLED TO MAINT

AIN

INTRINSIC SAFETY

! OPERA

TING THE SYSTEM WITH

THIS COVER REMOVED COULD RESUL

T IN

AN

EXPLOSION HAZARD. CONSUL

T THE INST

ALLA

T

IO

N

MANUAL

FOR MORE INFORMA

TION.

Intrinsically Safe Liquid Level Probe & Leak

Detection Sensor Cover

Write-in circuit I.D. label

(Probe/Sensor: Type & Location...

Input Source/Relay Output Destination)

Space for optional TS-IEM Module # 1

Space for optional TS-IEM Module # 2