6level probe installation – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, 508 & 750) Installation User Manual
Page 35
LEVEL PROBE INSTALLATION
Page
6 - 1
6
6
Level Probe Installation
Installation Preparation
The level probes are installed in underground storage tanks (USTs) and
aboveground storage tanks (ASTs) and are suspended by a chain. The probes are
designed to fit inside 4-inch (101.6 mm) riser pipes. Before starting the probe
installation, be sure that you have the necessary hardware: level probe(s), product
and water interface floats, and the TSP-K4A probe installation kit(s) on hand. Parts
supplied with the TSP-K4A probe installation kit are identified with an asterisk (
*
)
below. For each tank, locate the following items:
a
Level probe
b
Product float
c
Water interface float — optional — only used with Petroleum Applications
d
*
Threaded adjustment eye bolt and suspension chain (with wing nut and split
ring attached)
e
*
Steel Support plate (with rubber grommet and insulating washer installed),
f
*
Four inch NPT (101.6 mm) riser cap adapter
g
*
Riser cap
h
*
Compression gland seal fitting (cord grip)
i
*
(3) Moisture resistant, no-strip, electrical wire splice connectors
The TS-504 and TS-508 tank gauges (
T4 T8
) are inventory only systems and use
the
TSP-LL2-__I inventory only probes. These probes are installed and wired the
same and look the same as the black-headed
TSP-LL2-__ probe except that the
TSP-LL2-__I has a yellow-tinted head.
Chemical Applications require different probes and parts for the installation. All are
made out of # 316 stainless steel and they are the:
TSP-LL2C-__ probe with a
swagelock fitting and float retainer assembly, the TSP-SSP float, and the
TSP-K4AS riser cap adapter. The
TSP-LL2C-__ probe installation details are
shown later in this chapter.
Product Codes:
T1
= TS-1001,
T2
= TS-2001,
T4
= TS-504,
T7
= TS-750,
T8
= TS-508,
none = all products
NOTE
NOTE