beautypg.com

6level probe installation – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, 508 & 750) Installation User Manual

Page 35

background image

LEVEL PROBE INSTALLATION

Page

6 - 1

6

6

Level Probe Installation

Installation Preparation

The level probes are installed in underground storage tanks (USTs) and
aboveground storage tanks (ASTs) and are suspended by a chain. The probes are
designed to fit inside 4-inch (101.6 mm) riser pipes. Before starting the probe
installation, be sure that you have the necessary hardware: level probe(s), product
and water interface floats, and the TSP-K4A probe installation kit(s) on hand. Parts
supplied with the TSP-K4A probe installation kit are identified with an asterisk (

*

)

below. For each tank, locate the following items:

a

Level probe

b

Product float

c

Water interface float — optional — only used with Petroleum Applications

d

*

Threaded adjustment eye bolt and suspension chain (with wing nut and split

ring attached)

e

*

Steel Support plate (with rubber grommet and insulating washer installed),

f

*

Four inch NPT (101.6 mm) riser cap adapter

g

*

Riser cap

h

*

Compression gland seal fitting (cord grip)

i

*

(3) Moisture resistant, no-strip, electrical wire splice connectors

The TS-504 and TS-508 tank gauges (

T4 T8

) are inventory only systems and use

the

TSP-LL2-__I inventory only probes. These probes are installed and wired the

same and look the same as the black-headed

TSP-LL2-__ probe except that the

TSP-LL2-__I has a yellow-tinted head.

Chemical Applications require different probes and parts for the installation. All are
made out of # 316 stainless steel and they are the:

TSP-LL2C-__ probe with a

swagelock fitting and float retainer assembly, the TSP-SSP float, and the
TSP-K4AS riser cap adapter. The

TSP-LL2C-__ probe installation details are

shown later in this chapter.

Product Codes:

T1

= TS-1001,

T2

= TS-2001,

T4

= TS-504,

T7

= TS-750,

T8

= TS-508,

none = all products

NOTE

NOTE