Pulse width

The pulse width for totalizer pulse output is set.
If Automatic setting (1:AUTO) is selected for pulse width mode, it is not necessary to set the pulse
width.
• The pulse width must be set to a value within the range of 0.3ms to 500ms. If you try to set a

value exceeding 500 ms, the value will be forcibly changed to 500ms.

• The pulse width must be set to 40% or less of the pulse period at 100% output. If a value

exceeding this limit is tried to set, regardless of the range described above, an error message
* H. OVER SPEC
appears and the value returns to the previously set value. Try to set a new value again.
If the pulse width is set to 0, it will be automatically set to 40% of the pulse period at 100% output.
However, if the calculation result exceeds 100ms, it will be forcibly set to 100ms.

Example 1 In the case of the following:

Range: 3,600m

3

/h (1m

3

/s)

Count rate: 0.001m

3

Since the count rate is 3,600 m

3

/h

÷ 0.001(m

3

) = 3,600,000 pulses/h (1000 pulses/s),

the full-scale period is 1s

÷ 1000 = 1ms.

Therefore, the pulse width can only be set to 1ms x 0.4 = 0.4ms.

Example 2 In the case of the following:

Rage: 3,600m

3

/h (1m

3

/s)

Count rate: 1000m

3

Since the pulse count is 3,600m

3

/h

÷ 1000m

3

= 3.6 pulses/h (0.001 pulse/s), the

full-scale period is 1s

÷ 0.001 = 1000s.

Therefore, the pulse width becomes 1000s

× 0.4 = 400s. However, since the maximum

value is 500ms, the pulse width becomes 500ms.

Example 3 In the case of the following:

Rage: 3,600m

3

/h (1m

3

/s)

Count rate: 1m

3

Pulse width is set to 0ms

Since the pulse count is 3,600m

3

/h

÷ 1m

3

= 3600 pulses/h (1 pulse/s), the full-scale

period is 1s

÷ 1 = 1s.

Therefore, the pulse width becomes 1s

× 0.4 = 400ms. However, in the case of

automatic setting, since the maximum value is 100ms, the pulse width becomes
100ms.