- 146 -

10.7

Remote Still Water Zero Adjustment

Still water zero adjustment can be performed using an external signal.

To use this function, follow the procedure in 8.2.14, “Digital I/O Function” and set the DI as a zero
adjustment start signal.

[Signal input condition]

Zero adjustment signal

10 seconds

20 seconds

Zero

adjustment

start

H level signal

L level signal

* The signal must be set to H level first and then it must go to L level 10 seconds later but not more

than 20 seconds, and then zero adjustment starts at the falling edge of the signal.
If the signal stays in H level less than 10 seconds or more than 20 seconds, the signal will be
ignored.