Toshiba Tohsiba Electromagnetic Flowmeter Converter L5232 User Manual
Page 84
6F8A0917
- 83 -
8.2.11 Current Output Setting Used When an Alarm Occurs
The current output value setting used when an alarm occurs is the function to fix the current output to
a pre-selected value if a fluid empty alarm or a self-diagnosis alarm occurs.
For the type of alarms to fix the current output, see the alarm output factor setting in 8.2.19
“Self-Diagnosis Function.”
Select the current output value used when an alarm occurs from the table shown below.
Current output setting function used when an alarm occurs
Selection
Current output value when an alarm occurs
1:UNDER 3.0mA
3.0mA or less
2:4.0mA
4.0mA
3:HOLD
Fixed to the current output
4:OVER 24.0mA
24.0mA or more
Checking the current output value used when an alarm occurs
Proceed as follows to check the current output value used when an alarm occurs.
Switch operation
Display example
Description
D3: 4-20 ALM.OUT
2:4.0mA
Select D3: 4
−20 ALM. OUT from the setting item selection
menu.
The currently set current output value used when an alarm
occurs appears.
D3: 4-20 ALM.OUT
Returns to the menu of setting item selection.