Toshiba Tohsiba Electromagnetic Flowmeter Converter L5232 User Manual
Page 117
6F8A0917
- 116 -
Changing the fixed output function
The following is an example to change the fixed output function from Fixed value output OFF to
ON and then go on to set the current output value and the pulse output value. To change the current
output value or pulse output value independently, select the following function:
Fixed current output value
N2: FIX CURR
Fixed pulse output value
N3: FIX PULSE
Switch operation
Display example
Description
N1: FIXED OUT
2:OFF
Select N1: FIXED OUT from the setting item selection menu.
The currently set fixed value output On/Off setting appears.
N1: FIXED OUT
2:OFF
The cursor appears.
N1: FIXED OUT
1:ON
Select the fixed value output: ON.
N2: FIX. CURR.
10.0 mA
The display blinks and the set value is displayed for
conformation.
Press
MENU/ENT
again to write the data. The cursor
disappears and then the current output set value can be
changed.
N2: FIX. CURR.
10.0 mA
Move the cursor to the desired digit to change.
N2: FIX. CURR.
20.0 mA
Change the number of the digit.
To change other digit, press
under this condition to move
the cursor to the desired digit and change the number there.
N3: FIX. PULSE
100 PPS
The display blinks and the set value is displayed for
conformation.
Press
MENU/ENT
again to write the data. The cursor
disappears and then the pulse output set value can be changed.
N3: FIX. PULSE
100 PPS
The display blinks and the set value is displayed for
conformation.
Press
MENU/ENT
again to write the data. Then the cursor
disappears and the display returns to the condition that the
setting value is displayed.
N3: FIX. PULSE
Returns to the menu of setting item selection.
Note. If a value outside of the settable range is tried to set, the upper limit or lower limit value of the settable
range will be forcibly set.