11.3

Cautionary Notes on Communications

Observe the following limitations when you communicate with flowmeter using HHT.

Current output load

(1) Load resistance: 240

Ω to 1kΩ (including communications line resistance)

(2) Load capacitance: 0.25

μF maximum (including communications line capacitance)

(3) Load inductance: 4mH maximum (including communications line inductance)

(For maximum cable length, about 2km is a guideline length when CVV-S
1.25mm

2

is used.)

Wiring cable

Use a shielded cable (CVV-S, etc) for wiring.

Interference on 4 to 20mA current signal

To communicate with the flowmeter, a digital signal (amplitude 0.4 to 0.8 V in the case of 500Ω
load resistance) with a frequency of 1.2 to 2.2 kHz is superimposed on the 4 to 20mA current signal.
If a receiving instrument with fast response time is connected to the analog current output line, the
superimposed communications signal may interfere with the output. To prevent this interference,
put a low-pass filter with a time constant of about 100 ms into the input circuit of the receiving
instrument.

C

R

Current output line

Load resistor

Converter

Filter

Receiving instrument

Figure 11.3 Filter Connection Example