Toshiba Tohsiba Electromagnetic Flowmeter Converter L5232 User Manual
Page 144
6F8A0917
- 143 -
Preset counter output performance
• Example to reset the totalizer using an external signal input
(When preset output level hold (Contact ON) is set)
ON
OFF
0
Reset/Start signal
(DI control signal level H)
Totalizer flow count
Preset output
Counter reset
Counter start
H level input
L level input
Preset count
set-point value
Counter reset
Input/Output Timing Chart
* When the Reset/Start signal is in H level (DI counter control signal level: H), the totalizer is reset to
zero and stops counting. When the Reset/Start signal goes to L level, the totalizer starts counting.
The preset output goes ON when the totalizer count exceeds the preset value, and the output goes
OFF when the totalizer is reset to zero.