Preset counter output performance

• Example to reset the totalizer using an external signal input

(When preset output level hold (Contact ON) is set)

ON

OFF

0

Reset/Start signal
(DI control signal level H)

Totalizer flow count

Preset output

Counter reset

Counter start

H level input

L level input

Preset count
set-point value

Counter reset

Input/Output Timing Chart

* When the Reset/Start signal is in H level (DI counter control signal level: H), the totalizer is reset to

zero and stops counting. When the Reset/Start signal goes to L level, the totalizer starts counting.
The preset output goes ON when the totalizer count exceeds the preset value, and the output goes
OFF when the totalizer is reset to zero.