Toshiba Tohsiba Electromagnetic Flowmeter Converter L5232 User Manual
Page 91
6F8A0917
- 90 -
Digital Input Function
DI FUNCT.
Digital input function
1: NO USE
Not used
2: C STA/STP
Totalizer Start/Stop control
3: C RES/STA
Totalizer Reset/Start control
4: RANGE SW1
Multi-range external switching signal 1
5: ZERO ADJ
Still water zero adjustment start
6: FIXED OUT
Fixed-value output mode control
7: RANGE SW2
Multi-range external switching signal 2
Level setting for digital input control signal
(for totalizer control only)
For totalizer control (items indicated by above), the operating level (active level) for input control
signal can be selected for each DI terminal.
DI DET LEVEL
Control signal level
1: L LEVEL
Low level active
2: H LEVEL
High level active
The operation for control signal input is shown below depending on the active level setting.
Digital input function setting
Control signal
level setting
Operation when control signal is input
L LEVEL
High signal: Totalization Stop
Low signal: Totalization Start
CNT STA/STP
(Totalizer Start/Stop)
H LEVEL
High signal: Totalization Start
Low signal: Totalization Stop
L LEVEL
High signal: Totalization Start
Low signal: Totalization Reset
CNT RES/STA
(Totalizer Reset/Start)
H LEVEL
High signal: Totalization Reset
Low signal: Totalization Start