Toshiba Tohsiba Electromagnetic Flowmeter Converter L5232 User Manual

Page 85

background image

6F8A0917

- 84 -

Changing the current output value used when an alarm occurs

The following is an example to show how to change the current output value, which is used when
an alarm occurs, from 4.0mA (2: 4.0mA) to 24.0mA or more (4: OVER 24.0mA).

Switch operation

Display example

Description

D3: 4-20 ALM.OUT
2:4.0mA

Select D3: 4

−20 ALM. OUT from the setting item selection

menu.
The currently set alarm output value used when an alarm
occurs appears.

D3: 4-20 ALM.OUT
2:4.0mA

The cursor appears.

D3: 4-20 ALM.OUT
4:OVER 24.0mA

Press

to select 4: OVER 24.0mA.

D3: 4-20 ALM.OUT
4:OVER 24.0mA

The display blinks and the set value is displayed for

confirmation.

Press

MENU/ENT

again to write the data. Then the cursor

disappears and the display returns to the condition that the

setting value is displayed.

D3: 4-20 ALM.OUT

Returns to the menu of setting item selection.