Page 104
6F8A0917
- 103 -
Changing the high/low limit alarm On/Off
The following is an example to change the high limit alarm setting from OFF to ON.
To change other high/low limit alarm On/Off setting, select the following functions.
High limit alarm On/Off
J1: H ALM SET
Low limit alarm On/Off
J3: L ALM SET
High-high limit alarm On/Off
K1: HH ALM SET
Low-low limit alarm On/Off
K3: LL ALM SET
Switch operation
Display example
Description
J1: H ALM SET
2:OFF
Select J1: H ALM SET from the setting item selection menu.
The currently set On/Off setting for high limit alarm appears.
J1: H ALM SET
2:OFF
The cursor appears.
J1: H ALM SET
1:ON
Change the setting.
J1: H ALM SET
1:ON
The display blinks and the set value is displayed for
confirmation.
Press
MENU/ENT
again to write the data. Then the cursor
disappears and the display returns to the condition that the
setting value is displayed.
J1: H ALM SET
Returns to the menu of setting item selection