Toshiba Tohsiba Electromagnetic Flowmeter Converter L5232 User Manual

Page 116

background image

6F8A0917

- 115 -

Fixed pulse output value

The pulse frequency is set, which is used to output in the fixed output mode through the DO
terminal where the pulse output function is set.
The fixed pulse output value can be set within the range of 0 to 1000pps in increments of 1pps.

Note: When the pulse output is sent out from DO2 terminal, up to 100pps can be output.

Checking the fixed output function setting

Proceed as follows to check the fixed output function.
How to check the fixed value out On/Off setting is shown here.
To check other settings, select the following functions:

Fixed current output value

N2: FIX CURR

Fixed pulse output value

N3: FIX PULSE

Switch operation

Display example

Description

N1: FIXED OUT
1:ON

Select N1: FIXED OUT from the setting item selection menu.
The currently set fixed value output On/Off setting appears.

N1: FIXED OUT

Returns to the menu of setting item selection.