6F8A0917

- 78 -

Changing the hysteresis

The hysteresis value is set to 3% unless otherwise specified when the converter is shipped from the
factory.
The following is an example to show how to change the hysteresis value from 3% to 5%.

Switch operation

Display example

Description

C6: RANGE HYST
03.0 %

Select C6: RANGE HYST from the setting item selection
menu.
The currently set hysteresis value appears. (Note)

C6: RANGE HYST
03.0 %

The cursor appears.

C6: RANGE HYST
03.0 %

Move the cursor to the desired digit to change.

C6: RANGE HYST
05.0 %

Change the number of the digit.
To change other digit, press

under this condition to move

the cursor to that digit and change the number there.

C6: RANGE HYST
05.0 %

The display blinks and the set value is displayed for

confirmation.

Press

MENU/ENT

again to write the data. Then the cursor

disappears and the display returns to the condition that the

setting value is displayed.

C6: RANGE HYST

Returns to the menu of setting item selection.

Note: If you try to set a value exceeding 25.0%, *H. OVER SPEC.* appears and the value returns to

the previously set value. Try to set a new value again.