5.6 Cautionary Notes on Replacing Converter

5.6.1 Replacing the LF230 Converter

The following precautions must be taken to replace the conventional type LF230 with LF232.

Installation

• Since the hole diameter and pitch for mounting fitting, and the dimensions of the LF232 converter

main unit are the same as those of the LF230 converter, it is possible to replace the converter without
changing the mounting panel, installation space, etc.

• The operation switches of the LF232 are infrared switches. If direct sunlight hits the display and the

operation section or if there is something nearby that easily reflects light, this kind of light becomes
disturbance light and the switch operation may not work correctly. Be careful about the installation
location and angle, or take measures such as providing a sunshade or shield plate so that disturbance
light does not hit the operation section directly.

Wiring

• The positions of the LF232 cable ports are the same as those of the LF230.
• The specifications of the cable ports differ as shown in the table below.

Table 5.2 Comparison of Cable Port Specifications

LF230

LF232

Ports on the housing

M27 fine pitch thread
Depth 0.433 inch (11mm)

G1/2
Depth 0.433 inch (11mm)

Material

Stainless steel

Nylon resin

Attached cable
connection
specifications

Waterproof grade

IP67

IP67

Appropriate cable
diameter

Excitation and DI/DO cables

φ0.433−0.512 inch
(

φ11−13mm)

Other cables

φ0.394−0.472 inch
(

φ10−12mm)

φ0.433−0.512 inch
(

φ11−13mm)

Conduit connection port R (PT) 1/2 male thread

Not provided

Blind plate (seal plate)

Waterproof blind plate
attached

Dustproof blind plate attached
* (Note)

Note: The blind plate is not a waterproof type. If it is necessary to install the converter where waterproof

structure is needed, take waterproof measures for unused cable ports such as using sealing plugs sold on
the market.


• Since the terminal block specification of the LF232 is M4 screws, the same as that of the LF230, it is

possible to connect the cables without changing the cable terminals.