6F8A0917

- 113 -

No.

Parameter name

Initial setting values

H1

Count rate

Meter size

1/10" to 1/4"

(

2.5 to 6 mm)

1L

Meter

size

1/2" to 1 1/2”

(

15 to 40 mm)

0.01m

3

Meter

size

2" to 4” (

50 to 100mm)

0.1m

3

Meter size 6” to 24” (150 to 600mm)

1m

3

Meter size 28” to 120” (700 to 3000mm)

10m

3

H2

Pulse width setting mode

AUTO

H3 Pulse

width

100

ms

I1 Preset

count

value

00000000

I2

Preset output function

HOLD

J1

High limit alarm setting

OFF

J2

High limit alarm value

0.0 %

J3

Low limit alarm setting

OFF

J4

Low limit alarm value

0.0 %

K1

High-high limit alarm setting

OFF

K2

High-high limit alarm value

0.0 %

K3

Low-low limit alarm setting

OFF

K4

Low-low limit alarm value

0.0 %

L1

Fluid empty alarm

ON Detection level: NORMAL
(In the case of LF232*F; OFF)

L2 Self-diagnosis

function

ON

L3

Alarm output factor setting

WITHOUT EMP (fluid empty alarm not included)

0.0 %

M1 Rate-of-change

limit

For partially filled pipes detectors: 10 %

0 s

M2 Control

time

For partially filled pipes detectors: 10 s

N1

Fixed value output function

OFF

O1

Zero offset

0.0 %