Toshiba Tohsiba Electromagnetic Flowmeter Converter L5232 User Manual
Page 114
6F8A0917
- 113 -
No.
Parameter name
Initial setting values
H1
Count rate
Meter size
1/10" to 1/4"
(
2.5 to 6 mm)
1L
Meter
size
1/2" to 1 1/2”
(
15 to 40 mm)
0.01m
3
Meter
size
2" to 4” (
50 to 100mm)
0.1m
3
Meter size 6” to 24” (150 to 600mm)
1m
3
Meter size 28” to 120” (700 to 3000mm)
10m
3
H2
Pulse width setting mode
AUTO
H3 Pulse
width
100
ms
I1 Preset
count
value
00000000
I2
Preset output function
HOLD
J1
High limit alarm setting
OFF
J2
High limit alarm value
0.0 %
J3
Low limit alarm setting
OFF
J4
Low limit alarm value
0.0 %
K1
High-high limit alarm setting
OFF
K2
High-high limit alarm value
0.0 %
K3
Low-low limit alarm setting
OFF
K4
Low-low limit alarm value
0.0 %
L1
Fluid empty alarm
ON Detection level: NORMAL
(In the case of LF232*F; OFF)
L2 Self-diagnosis
function
ON
L3
Alarm output factor setting
WITHOUT EMP (fluid empty alarm not included)
0.0 %
M1 Rate-of-change
limit
For partially filled pipes detectors: 10 %
0 s
M2 Control
time
For partially filled pipes detectors: 10 s
N1
Fixed value output function
OFF
O1
Zero offset
0.0 %