6F8A0917

- 144 -

• Example to reset the totalizer using an external signal input (When one-shot pulse output is set)

ON

OFF

0

Reset/Start signal
(DI control signal level L)

Totalizer flow count

Preset output

Counter reset

Counter start

H level input

L level input

Preset count
set-point

Counter reset

Preset output is OFF
because Counter is reset.

Preset output OFF because
pulse width is reached.

Input/Output Timing Chart

* When the Reset/Start signal is in L level (DI counter control signal level: L), the totalizer is reset to

zero and stops counting. When the Reset/Start signal goes to H level, the totalizer starts counting.
The preset output goes ON when the totalizer count exceeds the preset value, and the output goes
OFF when the pulse width is reached or the totalizer is reset to zero.