8.2.17 Flow Rate High/Low limit Alarm

The flow rate high/low limit alarm is the function to generate an alarm when the instantaneous flow
rate exceeds a preset high limit value (or low limit value).
When an alarm is generated, an alarm message is displayed and a signal can be output through DO.
Two outputs are provided each for high limit value and low limit value (4 outputs in total of high limit,
high-high limit, low limit and low-low limit) and an alarm output can be sent out separately.

The following parameters can be set here:

(1) High limit alarm On/Off

(2) High limit value

(3) Low limit alarm On/Off

(4) Low limit value

(5) High-high limit alarm On/Off

(6) High-high limit value

(7) Low-low limit alarm value On/Off

(8) Low-low limit value

Note

• To output a high/low limit alarm through DO, it is necessary to set the DO function for output.

For how to set the DO function, see 8.2.14 “Digital I/O Function.”

High/low limit alarm On/Off

Whether the high/low limit alarm is used or not can be selected

Selection Alarm

operation

1: ON

Alarm function provided

If the flow rate exceeds a selected high limit value (or low limit value),
an alarm is generated.

2: OFF

Alarm function not provided

The selected alarm will not be generated.

High/low limit value

A flow rate value (high/low limit value) to generate an alarm is set in percent of the maximum
range (Range 1) flow rate value.
The high/low limit alarm value can be set within the range of

−10% to 110% in increments of 0.5%.