beautypg.com

9 damping constant – Toshiba Tohsiba Electromagnetic Flowmeter Converter L5232 User Manual

Page 80

background image

6F8A0917

- 79 -

8.2.9 Damping

Constant

The damping constant is set to average out the output fluctuations. (The larger the damping constant,
the more the output is averaged and the fluctuations can be reduced but the response becomes slower.)

The damping constant can be set from 0.0sec, 0.5sec, and 1 to 60sec (1sec each).
(If detector is partially filled pipes type, the damping constant can be set from 0.0sec, 5sec, and 10 to
600sec (1sec each).)
Note: If 0.0 sec is set, the damping constant becomes a value equivalent to 0.1 sec.

If you set a value exceeding 60s, it is forcibly changed to 60s before data is written.

Checking the damping constant

Proceed as follows to check the damping constant.

Switch operation

Display example

Description

D1: DAMPING
02.0 s

Select D1: DAMPING from the setting item selection menu.
The currently set damping constant appears.

D1: DAMPING

Returns to the menu of setting item selection.