6F8A0917

- 168 -

5. Display/setting items

• Output display: 16-character × 2-line dot-matrix LCD (with back light)

Indicating unit: 2 units can be selected from the flowing units: flow velocity, instantaneous

flow rate, total flow (forward/reverse/difference flow), total count, %, custom
unit.

• Setting: Various parameters can be set without opening the converter housing using 4 infrared

switches (password can be set)
Settable also with AF900 Handheld terminal

• Damping: 0.5 to 60 seconds (settable in increments of 1 second)

• Zero adjustment: Adjustable with infrared switches

•“Field re-verification” Mag-Prover – Toshiba’s Zero span calibration tool :

Allows unit to be re-calibrated and verified using internal software program
(for more information contact Toshiba International Corp.)

• Operation at power failure:

Various setting values are stored in non-volatile memory.
Current output 0mA
Digital Output OFF (contact open)
Display Unlit

6. Other items

• Mass: Approx. 18 lb (8kg) (including a mounting fitting)

• Ambient temperature: -4 to 140 °F (-20 to 60 °C)

(storage temperature: -13 to 149 °F (-25 to 65 °C))

• Arrester: Included in the power supply circuit, current signal output circuit and digital I/O

circuit.

• Terminal block structure: 21-pole, screw connection type (M4 screw)

• Housing material: Aluminum alloy

• Painting: Acryl resin baked painting with pearl gray color

• Structure: IP 67

• Cable ports: G (PF) 1/2 female thread with cable connection

Adaptable cable diameter: φ0.433 to 0.512 inch (φ11 to 13mm)
Material: Nylon 66

• Vibration resistance: No resonance point exists when the following vibration is applied:

10 to 55Hz with amplitude of 0.07mm,
No problem occurs when vibration of 30Hz, 29.4m/s

2

is applied in each

direction for 4 hours each.

Note: If the flowmeter is intended to be used in a location where vibration is applied constantly,

contact Toshiba.