Changing the damping constant

The following is an example to show how to change the damping constant from 0.5 sec to 10 sec.

Switch operation

Display example

Description

D1: DAMPING
00.5 s

Select D1: DAMPING from the setting item selection menu.
The currently set damping constant (0.5 s in this example)
appears.

D1: DAMPING
00.5 s

The cursor appears.
Press

further to move the cursor to the desired digit to

change.

D1: DAMPING
10.5 s

10.0 s

Change the number of the digit.
To change other digit, press

under this condition to move

the cursor to that digit and change the number these.

D1: DAMPING
10.0 s

The display blinks and the set value is displayed for

confirmation.

Press

MENU/ENT

again to write the data. Then the cursor

disappears and the display returns to the condition that the

setting value is displayed.

D1: DAMPING

Returns to the menu of setting item selection.

Note: If you set a value exceeding max value, it is forcibly changed to max value before data is

written.