Diagnostic Data of the Signal Modules

B-19

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Bytes 8 to 23 of the SM 431; AI 8

16 Bit

Data record 1 with bytes 8 to 23 contains channel-specific diagnostic data. The
following figure shows the assignment of the even diagnostic bytes (bytes 8, 10, to
22) for a channel of the module.

7 6

0

Configuring/parameter assignment error

Wire break

Underflow

Overflow

5 4 3 2 1

0

0

0

Reference channel error

Figure B-26

Even Diagnostic Byte for a Channel of the SM 431; AI 8 x 16 Bit

The following figure shows the assignment of the odd diagnostic bytes (bytes 9,
11, to 23) for a channel of the module.

7 6

0

Run time calibration error

5 4 3 2 1

0

User calibration doesn’t correspond to the parameter assignment

0

0

0 0 0

Figure B-27

Odd Diagnostic Byte for a Channel of the SM 431; AI 8 x 16 Bit