Interface Submodules

13-20

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Default Settings in the BIOS

The following I/O addresses and interrupt numbers are set as defaults in the BIOS
for LPT ports:

Port

I/O Address

Interrupt No.

With mass storage module MSM 478

LPT1 (on MSM 478)

03BCH

7

LPT2 (IF 962-LPT)

0378H

5

Without mass storage module MSM 478

LPT1 (IF 962-LPT)

0378H

7

LPT2 (IF 962-LPT)

0278H

5

Configuration register

The BIOS setup defines in which AT-compatible I/O address area the LPT interface
is to be operated or whether it is only to be operated in the reserved I/O address
area and this information is stored in the configuration register. Tables 13-18 to
13-20 give you an overview of the possible settings in the configuration register.

Table 13-18

Offset Address for the Configuration Register (IF 962-LPT)

Offset

Address

Function

Remarks

0

H

Configuration register

Read/write

Table 13-19

Meaning of the Data Bits in the Configuration Register (IF 962-LPT)

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Write: Any (“0” or “1”)

Read: Always “1”

Addressing type LPT