Analog Modules

5-93

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Suppression of interference, Limits of Error

Interference voltage suppression parameterized for
f = nx (f1

"

1%), (f1 = interference frequency) n = 1, 2 ,

...
filter 400/60/50 Hz

Common-mode
interference
(U

CM

< 11 V

ss

)

> 80 db

Series-mode interference
(peak value of interference
< rated value of input
range)

> 40 dB

Crosstalk between the inputs

> 70 dB

Operational limit (in the entire temperature range, with
reference to the input range)

Voltage input

"+

1 V

"

10 V

1 V to 5 V

"

0.7 %

"

0.9 %

"

0.9 %

Current input

"

20 mA

4 mA to 20 mA

"

0.8%

"

0.8%

Resistance test

0...600

W

;

"

1.0%

Basic error (operational limit at 25

°

C, referred to input

range)

Voltage input

"

1 V

"

10 V

1 ... 5 V

"

0.6%

"

0.75%

"

0.75%

Current input

"

20 mA

4 mA to 20 mA

"

0.7%

"

0.7%

Resistance test

0 to 600

W

;

"

0.7%

Temperature error (with
reference to the input range)

"

0,03% K

Linearity error (with reference
to the input range)

"

0,05% K

Repeat accuracy (in the steady
state at 25

°

C, referred to the

input range)

"

0.2%

Status, Interrupts, Diagnostics

Interrupts

None

Diagnostic functions

None

Substitute value can be applied

No

Data for Selecting a Sensor

Input range (rated values)/Input
resistance

Voltage

"

1 V/10 M

W

"

10 V/10 M

W

1 V to 5 V

/

10 M

W

Current

"

20 mA/50

W

4 mA to 20 mA

/

50

W

Resistors

0 to 600

W/

10 M

W

Maximum input voltage for
voltage input
(destruction limit)

Max. 18 V continuous;
75 V for 1 ms (cycle
factor 1 : 20)

Maximum input current for
current input (destruction limit)

40 mA continuous

Connection of the signal
sensor

For measuring voltage

Possible

For measuring current

As two-wire
transmitter

Possible

As four-wire
transmitter

Possible

For measuring resistance

With two-conductor
terminal

With three-conductor
terminal

Possible; cable
resistance is also
measured

With four-conductor
terminal

Possible

Load of the two-wire
transmitter

Max. 750

W

Characteristic linearization

No

This manual is related to the following products: