Analog Modules

5-26

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Analog Value Representation in Voltage Output Ranges

Table 5-34 Analog Value Representation in Output Range

±(

10 V

System

Voltage Output Range

Dec.

Hex.

±(

10 V

118.5149% 32767

7FFF

0.00 V

Overflow, off circuit and deenergized

32512

7F00

g

117.589% 32511

7EFF

11.76 V

Overrange

27649

6C01

100% 27648

6C00

10 V

75% 20736

5100

7.5 V

0.003617% 1

1

361.7

µ

V

Rated range

0% 0

0

0 V

–1

FFFF

– 361.7

µ

V

– 75% – 20736

AF00

– 7.5 V

– 100% –27648

9400

– 10 V

–27649

93FF

Underrange

–117.593% –32512

8100

– 11.76 V

– 32513

80FF

Underflow, off circuit and deenergized

– 118.519% –32768

8000

0.00 V

g

Table 5-35 Analog Value Representation in Output Ranges 0 to 10 V and 1 to 5 V

System

Voltage Output Range

Dec.

Hex.

0 to 10 V

1 to 5 V

118.5149% 32767

7FFF

0.00 V

0.00 V

Overflow, off circuit and
d

i

d

32512

7F00

deenergized

117.589% 32511

7EFF

11.76 V

5.70 V

Overrange

27649

6C01

g

100% 27648

6C00

10 V

5 V

75% 20736

5100

7.5 V

3.75 V

0.003617% 1

1

361.7

µ

V

1V+144.7

µ

V

Rated range

0% 0

0

0 V

1 V

–1

FFFF

Underrange

– 25% –6912

E500

0 V

g

–6913

E4FF

Not possible.
The output value is limited to

–117.593% –32512

8100

The output value is limited to
0 V.

– 32513

80FF

Underflow, off circuit and
d

i

d

– 118.519% –32768

8000

0.00 V

0.00 V

deenergized