beautypg.com

Siemens Simatic S7-400 User Manual

Page 423

background image

RS 485 Repeater

10-3

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

10.2

Appearance of the RS 485 Repeater;

(6ES7972-0AA01-0XA0)

The table below shows the appearance of the RS 485 repeater and lists its
functions.

Table 10-3 Description and Functions of the RS 485 Repeater

Repeater Design

No

.

Function

24 VDC

L+ M PE M 5.2

А

10

А

Connection for the RS 485 repeater power supply (pin “M5.2” is
the ground reference, if you want to measure the voltage
difference between terminals “A2” and “B2”).

А

Б

10

Б

Shield clamp for the strain relief and grounding of the bus cable
of bus segment 1 or bus segment 2

В

В

Terminals for the bus cable of bus segment 1

Â

A1

B1

A1

B1

Ã

Terminating resistance for bus segment 1

Г

Д

И

A1

B1

A1

B1

PG

OP

11

12

OFF

ON

DP1

Ä

Switch for OFF operating mode

(= isolate bus segments from each other – for example, for
startup

Å

OP

DP2

12

Å

Terminating resistance for bus segment 2

SIEMENS

ON

Æ

Terminals for the bus cable of bus segment 2

SIEMENS

RS 485-REPEATER

Æ

A2

B2 A2

B2

Ç

Slide for mounting and removing the RS 485 repeater on the
standard rail

Б

И

Interface for programming device/OP in bus segment 1

Á

10

LED 24 V supply voltage

Ç

11

LED for bus segment 1

12

LED for bus segment 2