Interface Submodules

13-32

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Status, Interrupts, Diagnostics

Status indicated

Interrupt

Diagnostic functions

1 sum interrupt from
up to 8 sources

No

Data for Selecting a Sensor

Input voltage

Nominal value

For signal “1”

For signal “0”

24 VDC

from 13 V to 30 V

- 30 V to + 5 V

Input current

At signal “1”

from 4 mA to 8.5 mA

Input delay time

750

µ

s or 3 ms

Input characteristic

In accordance with
IEC 1131, Part 2

Type of input in accordance
with IEC 1131

Type 1

Connection of 2-wire
BEROs

Permissible quiescent
current

Permissible supply
voltage

Possible under the
following
conditions:

v

1.5 mA

min. 22 V

Data for Selecting an Actuator

Output voltage

At signal “0”

At signal “1”

max. 3 V

L+ - 1.5 V

Output current

At signal “1”
nominal value
permissible range

At signal “0” (residual
current)

0.1 A

from 5 mA to 0.1 A

max. 100 mA

Lamp load

max. 2.4 W

Parallel wiring of 2 outputs

No

Setting a digital input

Yes

Switching frequency max.

With resistive load/lamp
load

At inductive load

500 Hz

2.0 Hz at 0.1 A

Inductive cutoff voltage
limited (internally) to

L+ - 39 V

Short-circuit protection of
the output

yes, electronically