Table 4-9
Diagnostic Messages of the Digital Modules, Causes of Errors and Remedial
Measures, continued
Diagnostic Message
Remedy
Possible Error Cause
Wire break
Lines interrupted
Close circuit
No external sensor supply
Wire sensors with 10 to 18 k
W
Channel not connected (open)
Disable the “Diagnostics – Wire Break”
parameter for the channel in STEP 7
Connect channel
Fuse blown
One or more fuses on the module
has blown and caused this fault.
Remove the overload and replace the
fuse
No sensor supply
Overload of sensor supply
Eliminate overload
Short circuit of sensor supply to M
Eliminate short circuit
No
l
d lt
L
Power supply L+ to module missing
Feed in supply voltage L+
load voltage L+
Fuse in module is defective
Replace module