beautypg.com

Siemens Simatic S7-400 User Manual

Page 282

background image

Analog Modules

5-66

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Table 5-47 Diagnostics Messages of the Analog Input Modules, Causes of Errors and Remedial

Measures, continued

Diagnostics

Message

Remedy

Possible Error Cause

EPROM error

The module is defective

Replace module

RAM error

ADC/DAC error

Hardware interrupt lost

The module cannot send an
interrupt, since the previous
interrupt was not acknowledged;
configuration error possible

Change interrupt handling in the CPU
(change priority for interrupt OB; shorten
interrupt program)

Configuring/parameter

i

t

Illegal parameters transferred to

d l

Check measuring range module

assignment error

module

Reassign module parameter

Short circuit to M

A short circuit to the M potential has
occurred on the sensor supply of
two-wire transmitters

Eliminate short circuit

Wire break

Resistance too high in the sensor
connection

Use different type of sensor or
connection, e.g. use conductors with a
larger cross-sectional core area

Open circuit between module and
sensor

Close circuit

Channel not connected (open)

Disable channel (“Measuring Type”
parameter)

Connect channel

Reference channel
error

The reference junction connected at
channel 0 is faulty due to a wire
break, for example

Check terminals

The reference temperature value
transferred is not within the value
range

Reparameterize the reference
temperature

Underflow

Input value violates underrange,
error may be caused:

Wrong measuring range selected

Configure other measuring range

With the measuring ranges 4 to
20 mA and 1 to 5 V, if necessary by
polarity reversal of sensor
connection

Check terminals

Overflow

Input value overflows overrange

Configure other measuring range

Run time calibration
error

A wiring fault has occurred on a
channel during the calibration cycle

Eliminate the wiring fault (fault remains
until the next calibration; in other words,
a maximum 6 minutes or until there is a
STOP-RUN transition of the CPU)

This manual is related to the following products: