beautypg.com

3 technical specifications, Technical specifications – Siemens Simatic S7-400 User Manual

Page 561

background image

Interface Submodules

13-65

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

13.9.3

Technical Specifications

Technical Specifications

The IF 964-DP interface submodule receives its supply voltage in the S7-400 from
the central processing unit and in the M7-400 from the programmable modules or
from the expansion modules. The current consumption given in the technical
specifications is the consumption required for dimensioning the power supply, that
is, the current consumption is referenced to 24 V in the M7-300 and to 5 V in the
M7-400.

6ES7964-2AA00-0AB0

6ES7964-2AA01-0AB0

Performance Features

Performance Features

Transmission rate

9.6 Kbps to 12 Mbps

Transmission rate

9.6 Kbps to 12 Mbps

Cable length

At 9.6 Kbps

At 12 Mbps

1200 m max.

100 m max.

Cable length

At 9.6 Kbps

At 12 Mbps

1200 m max.

100 m max.

Number of stations

125

Number of stations

125

Backup memory

(dual-port RAM)

256 Kbytes

Backup memory

(dual-port RAM)

256 Kbytes

Physical interface

RS485

Physical interface

RS485

Galvanic isolation

Yes

Galvanic isolation

Yes

Technical Specifications

Technical Specifications

Supply voltage

Supplied from the
M7-400 programmable
modules or from the
M7-300/400 expansion
modules

Supply voltage

Supplied from the
S7-400 or from the
M7-400 programmable
modules or from the
M7-300/400 expansion
modules

Current consumption in the
M7-300 (for dimensioning the
24 V power supply)

The module does not
consume any current at 24 V,
and it only makes this voltage
available at the DP interface.

Total current
consumption of the
components connected
to the DP interface,
with a maximum of 150
mA

Current consumption from the
S7-400 bus/in M7-300 (DC
24 V for the dimensioning of
the 24 V power supply)
The module does not
consume any current at 24 V,
and it only makes this voltage
available at the DP interface.

Total current
consumption of the
components connected
to the DP interface,
with a maximum of 150
mA

Current consumption in the
M7-400 (for dimensioning the
5 V power supply)

0.45 A

.

Current carrying capacity of
the isolated 5 V (P5

ext

)

Max. 90 mA

Current carrying capacity of
the isolated 5 V (P5

ext

)

Max. 90 mA

Load rating of the isolated 5V
(P5

ext

)

max. 90 mA

Load rating of the isolated 5V
(P5

ext

)

Load rating of the 24 V

max. 90 mA

max. 150 mA

Submodule ID

8C

H

Submodule ID

8C

H

Power losses

2 W

Power losses

2 W

Dimensions

W x H x D (mm)

18.2 x 67 x 97

Dimensions

W x H x D (mm)

18.2 x 67 x 97

Weight

0.065 kg

Weight

0.065 kg