3 technical specifications, Technical specifications – Siemens Simatic S7-400 User Manual
Page 561
Interface Submodules
13-65
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
13.9.3
Technical Specifications
Technical Specifications
The IF 964-DP interface submodule receives its supply voltage in the S7-400 from
the central processing unit and in the M7-400 from the programmable modules or
from the expansion modules. The current consumption given in the technical
specifications is the consumption required for dimensioning the power supply, that
is, the current consumption is referenced to 24 V in the M7-300 and to 5 V in the
M7-400.
6ES7964-2AA00-0AB0
6ES7964-2AA01-0AB0
Performance Features
Performance Features
Transmission rate
9.6 Kbps to 12 Mbps
Transmission rate
9.6 Kbps to 12 Mbps
Cable length
•
At 9.6 Kbps
•
At 12 Mbps
1200 m max.
100 m max.
Cable length
•
At 9.6 Kbps
•
At 12 Mbps
1200 m max.
100 m max.
Number of stations
≤
125
Number of stations
≤
125
Backup memory
(dual-port RAM)
256 Kbytes
Backup memory
(dual-port RAM)
256 Kbytes
Physical interface
RS485
Physical interface
RS485
Galvanic isolation
Yes
Galvanic isolation
Yes
Technical Specifications
Technical Specifications
Supply voltage
Supplied from the
M7-400 programmable
modules or from the
M7-300/400 expansion
modules
Supply voltage
Supplied from the
S7-400 or from the
M7-400 programmable
modules or from the
M7-300/400 expansion
modules
Current consumption in the
M7-300 (for dimensioning the
24 V power supply)
The module does not
consume any current at 24 V,
and it only makes this voltage
available at the DP interface.
Total current
consumption of the
components connected
to the DP interface,
with a maximum of 150
mA
Current consumption from the
S7-400 bus/in M7-300 (DC
24 V for the dimensioning of
the 24 V power supply)
The module does not
consume any current at 24 V,
and it only makes this voltage
available at the DP interface.
Total current
consumption of the
components connected
to the DP interface,
with a maximum of 150
mA
Current consumption in the
M7-400 (for dimensioning the
5 V power supply)
0.45 A
.
Current carrying capacity of
the isolated 5 V (P5
ext
)
Max. 90 mA
Current carrying capacity of
the isolated 5 V (P5
ext
)
Max. 90 mA
Load rating of the isolated 5V
(P5
ext
)
max. 90 mA
Load rating of the isolated 5V
(P5
ext
)
Load rating of the 24 V
max. 90 mA
max. 150 mA
Submodule ID
8C
H
Submodule ID
8C
H
Power losses
2 W
Power losses
2 W
Dimensions
W x H x D (mm)
18.2 x 67 x 97
Dimensions
W x H x D (mm)
18.2 x 67 x 97
Weight
0.065 kg
Weight
0.065 kg