beautypg.com

2 behavior of the sm 421; di 16 x 24 vdc – Siemens Simatic S7-400 User Manual

Page 160

background image

Digital Modules

4-38

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

4.10.2

Behavior of the SM 421; DI 16

24 VDC

Effect of Operating Mode and Supply Voltage on the Input Values

The input values of the SM 421; DI 16

24 DC depend on the operating mode of

the CPU and on the supply voltage of the module.

Table 4-14 How the Input Values Depend on the Operating Mode of the CPU and on the

Supply Voltage L+ of the SM 421; DI 16

24 VDC

CPU Operating Mode

Power Supply L+
to Digital Module

Input Value of Digital Module

POWER ON

RUN

L+ exists

Process value

L+ missing

0 signal *

STOP

L+ exists

Process value

L+ missing

0 signal*

POWER
OFF

L+ exists

OFF

L+ missing

*

Depends on the parameter assignment (see Table 4-13 )

Behavior upon Failure of the Supply Voltage

Failure of the supply voltage of the SM 421; DI 16

24 DC is always indicated by

the EXTF LED on the module. Furthermore, this information is made available on
the module (entry in diagnosis).

Triggering of the diagnostic interrupt depends on the parameter assignment
(see Section 4.9.1).

Short-Circuit of Sensor Supply Vs

Irrespective of the parameter assignment, the corresponding Vs LED goes out if a
short-circuit of the encoder supply Vs occurs.

This manual is related to the following products: