beautypg.com

B-15 – Siemens Simatic S7-400 User Manual

Page 589

background image

Diagnostic Data of the Signal Modules

B-15

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Bytes 4 to 8 of the SM 431; AI 16

16 Bit

Byte 4

7 6

0

5 4 3 2 1

Byte 5

7

0

Channel type B#16#71: analog input

Number of diagnostics bits that the module
outputs per channel: 8 bits long

Byte 6

7

0

Number of channels of the same
type in one module: 16 channels

Byte 7

7 6

0

Channel error, channel 0

Channel error, channel 1

Channel error, channel 6

Channel error, channel 7

5 4 3 2 1

...

0

Byte 8

7 6

0

Channel error, channel 14

Channel error, channel 15

5 4 3 2 1

...

Channel error, channel 8

Channel error, channel 9

Figure B-18

Bytes 4 to 8 of the Diagnostic Data of the SM 431; AI 16 x 16 Bit

Bytes 9 to 24 of the SM 431; AI 16 x 16 Bit

Data record 1 with bytes 9 to 24 contains the channel-specific diagnostic data. The
figure below shows the assignment of the diagnostic byte for a channel of the
module.

7 6

0

Configuring/parameter assignment error

Wire break

Underflow

Overflow

5 4 3 2 1

Short-circuit to M

Reference channel error

0

0

Figure B-19

Diagnostic Byte for a Channel of the SM 431; AI 16 x 16 Bit

This manual is related to the following products: