Analog Modules
5-20
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Analog Value Representation for Thermocouple Type L
Table 5-26 Analog Value Representation for Thermocouple Type L
Type L
Units
Type L
Units
Type L
Units
Type L
in
5
C
Decimal
Hexa-
decimal
Type L
in
5
F
Deci-
mal
Hexa-
deci-
mal
Type L
in K
Deci-
mal
Hexa-
decimal
Range
> 1150.0
32767
7FFF
H
> 2102.0
32767
7FFF
H
> 1423.2
32767
7FFF
H
Overflow
1150.0
:
901.0
11500
:
9010
2CEC
H
:
2332
H
2102.0
:
1653.8
21020
:
16538
521C
H
:
409A
H
1423.2
:
1174.2
14232
:
11742
3798
H
:
2DDE
H
Overrange
900.0
:
–200.0
9000
:
–2000
2328
H
:
F830
H
1652.0
:
–328.0
16520
:
–3280
4088
H
:
F330
H
1173.2
:
73.2
11732
:
732
2DD4
H
:
02DC
H
Rated range
< –200.0
< –2000
< F830
H
< –328.0
<
–3280
H < 73.2 < 732 <02DC H Underflow In the case of incorrect wiring (for example, polarity reversal or open inputs) or of a sensor error in the ...if F380 H is violated and outputs 8000 H ...if EAC0 H is violated and outputs 8000 H ...if FE2C H is violated and outputs 8000 H Analog Value Representation for Thermocouple Type N Table 5-27 Analog Value Representation for Thermocouple Type N Type N Units Type N Units Type N Units Type N in 5 C Deci- mal Hexade- cimal Type N in 5 F Deci- mal Hexa- deci- mal Type N in K Deci- mal Hexa- deci- mal Range > 1550.0 32767 7FFF H > 2822.0 32767 7FFF H > 1823.2 32767 7FFF H Overflow 1550.0 : 1300.1 15500 : 13001 3C8C H : 32C9 H 2822.0 : 2373.8 28220 : 23738 6E3C H : 5CBA H 1823.2 : 1574.2 18232 : 15742 4738 H : 3D7E H Overrange 1300.0 : –270.0 13000 : –2700 32C8 H : F574 H 2372.0 : –454.0 23720 : –4540 5CA8 H : EE44 H 1573.2 : 0 15732 : 0 3D74 H : 0000 H Rated range < –270.0 < < F574 H < –454.0 < H < 0 < 0 < H Underflow In the case of incorrect wiring (for example, polarity reversal or open inputs) or of a sensor error in the ...if F0C4 H is violated and outputs 8000 H ...if E5D4 H is violated and outputs 8000 H ...if FB70 H is violated and outputs 8000 H
negative range (for example, incorrect thermocouple type), the analog input module reports an
underflow...
–2700
–4540
0000
negative range (for example, incorrect thermocouple type), the analog input module reports an
underflow...