beautypg.com

B-16 – Siemens Simatic S7-400 User Manual

Page 590

background image

Diagnostic Data of the Signal Modules

B-16

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Bytes 2 and 3 of the SM 431; AI 8

RTD

16 Bit

Byte 2

7 6

0

Operating status 0: RUN

1: STOP

5 4 3 2 1

0

Byte 3

7 6

0

EPROM error

ADC/DAC error

Hardware interrupt lost

5 4 3 2 1

0

0 0 0 0

0

0

0 0

0

0

Figure B-20

Bytes 2 and 3 of the Diagnostic Data of the SM 431; AI 8 x RTD x 16 Bit

Bytes 4 to 7 of the SM 431; AI 8

RTD

16 Bit

Byte 4

7 6

0

5 4 3 2 1

Byte 5

7

0

Channel type B#16#71: analog input

Number of diagnostics bits that the module
outputs per channel: 16 bits long

Byte 6

7

0

Number of channels of the same
type in one module: 8 channels

Byte 7

7 6

0

Channel error, channel 0

Channel error, channel 1

Channel error, channel 6

Channel error, channel 7

5 4 3 2 1

...

...

...

...

...

0

Figure B-21

Bytes 4 to 7 of the Diagnostic Data of the SM 431; AI 8 x RTD x 16 Bit

This manual is related to the following products: