1 profibus dp master interface im 467/im 467 fo – Siemens Simatic S7-400 User Manual
Page 400
PROFIBUS DP Master Interface IM 467/IM 467 FO
8-2
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
8.1
PROFIBUS DP Master Interface IM 467/IM 467 FO
Order Numbers
IM 467
6ES7467-5GJ02-0AB0 (RS 485)
IM 467 FO
6ES7467-5FJ00-0AB0 (F0)
Application
PROFIBUS DP, standardized to IEC 61784–1:2002 Ed1 CP 3/1, enables rapid
communication in the field between programmable controllers, PCs and field
devices. Field devices are devices such as: ET 200 distributed I/O devices, drives,
valve terminals, switchgear and many others.
The IM 467/IM 467 FO interface module is meant to be used in an S7-400
programmable controller. It permits the S7-400 to be connected to PROFIBUS DP.
Note
The PROFIBUS DP master interface IM 467 or IM 467 FO is not a
DP master in accordance with DPV 1.
Configuration
•
Configured as for the S7-400
•
Can be operated without a fan
•
A maximum of 4 IM 467/IM 467 FO can be used in the central controller. There
are no slot rules.
•
The IM 467/IM 467 FO and the CP 443-5 Extended cannot be used together.
•
The transmission rate of 9.6 kbps to 12 Mbps can be set in steps using software
•
Configuration and programming are possible via PROFIBUS DP.
You must not, however, change the PROFIBUS DP parameters.
•
IM 467 with 9-pin subminiature D female connector for connection to
PROFIBUS DP (6ES7467-5GJ02-0AB0)
•
IM 467 FO with fiber-optic cable for connection to