PROFIBUS DP Master Interface IM 467/IM 467 FO

8-11

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Reusing Fiber-Optic Cables

Note
If you insert used fiber-optic cables in the plug-in adapter again, you must cut off
the bent lengths of both fiber-optic cable cores and install the Simplex connectors
again.
This avoids any attenuation losses due to parts of the cores of the fiber-optic
duplex cables being bent again and overstressed.

Inserting the Fiber-Optic Cables into the IM 467 FO

Insert the fiber-optic cables and attached plug-in adapters into the IM 467 FO.
Move the protruding handle of the plug-in adapter upwards.

Make sure that it is correctly positioned: The sender fiber-optic cable is plugged
into the receiver socket, and the receiver fiber-optic cable is inserted into the
sender socket of the fiber-optic interface of the IM 467 FO.

If the IM 467 FO is the last node in the fiber-optic network, you must close the
unoccupied fiber-optic cable interface with filler connectors (the connectors are
already in place when the IM 467 FO is delivered).

!

Caution
Do not look directly into the opening of the optical sender diodes.
The light beam could damage your eyes.

Handle

Sender

Receiver

PROFIBUS DP

Receiver

Receiver

Sender

Sender

R

T

R

T

Figure 8-7

Inserting the Fiber-Optic Cables into the IM 467 FO

Bending Radius for the Fiber-Optic Cable

Make sure when you wire the fiber-optic duplex cable cores and insert them into
the plug-in adapter that the permissible bending radius of 30 mm is not violated.
See also the installation guidelines on fiber-optic cables in the SIMATIC NET
PROFIBUS Networks manual.