Analog Modules

5-12

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Table 5-10 Analog Value Representation in the Voltage Measuring Ranges

±

500 mV to

±

25 mV

System

Voltage Measuring Range

Dec.

Hex.

±

500 mV

±

250 mV

±

80 mV

±

50 mV

±

25 mV

118.515%

32767

7FFF

592.6 mV

296.3 mV

94.8 mV

59.3 mV

29.6 mV

Overflow

117.593%

32512

7F00

117.589%

32511

7EFF

587.9 mV

294.0 mV

94.1 mV

58.8 mV

29.4 mV

Overrange

27649

6C01

100.000%

27648

6C00

500 mV

250 mV

80 mV

50 mV

25 mV

75%

20736

5100

375 mV

187.54 mV

60 mV

37.5 mV

18.75 mV

0.003617%

1

1

18.08

m

V

9.04

m

V

2.89

m

V

1.81

m

V

904.2 nV

Rated range

0%

0

0

0 mV

0 mV

0 mV

0 mV

0 mV

–1

FFFF

– 75.00%

– 20736

AF00

– 375 mV

–187.54 mV

– 60 mV

– 37.5 mV

– 18.75 mV

100.000%

–27648

9400

– 500 mV

– 250 mV

– 80 mV

– 50 mV

– 25 mV

–27649

93FF

Underrange

–117.593%

–32512

8100

– 587.9 mV

– 294.0 mV

– 94.1 mV

– 58.8 mV

– 29.4 mV

117.596%

– 32513

80FF

Underflow

118.519%

–32768

8000

– 592.6 mV

– 296.3 mV

– 94.8 mV

– 59.3 mV

– 29.6 mV

Table 5-11 Analog Value Representation in the Voltage Measuring Ranges 1 to 5 V and 0 to 10 V

System

Voltage Measuring Range

Dec.

Hex.

1 to 5 V

0 to 10 V

118.515% 32767

7FFF

5.741 V

11.852 V

Overflow

117.593% 32512

7F00

117.589% 32511

7EFF

5.704 V

11.759 V

Overrange

27649

6C01

100.000% 27648

6C00

5 V

10 V

75% 20736

5100

3.75 V

7.5 V

0.003617% 1

1

1 V + 144.7

m

V

0 V + 361.7

m

V

Rated range

0% 0

0

1 V

0 V

–1

FFFF

Underrange

– 17.593% –4864

ED00

0.296 V

Negative values not

ibl

– 4865

ECFF

g

possible

Underflow

v

–17.596% –32768

8000