beautypg.com

Siemens Simatic S7-400 User Manual

Page 303

background image

Analog Modules

5-87

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Measuring Ranges

You set the measuring ranges by means of the measuring range modules on the
module and the “Measuring Type” parameter in STEP 7.

Table 5-55 Measuring Ranges of the SM 431; AI 8 x 14 Bit

Method Selected

Measuring Range

(Type of Sensor)

Measuring Range

Module Setting

Description

U: Voltage

"

80 mV

"

250 mV

"

500 mV

"

1 V

A

You will find the digitized analog
values in Section 5.3.1 in the
voltage measuring range

"

2.5 V

"

5 V

1 to 5 V

"

10 V

2DMU: Current (two-wire
transmitter)

4 to 20 mA

D

To supply these transmitters with
current you must connect 24 V to
the L+ and M front connector
terminals.

You will find the digitized analog
values in Section 5.3.1 in the
current measuring range

4DMU: Current
(four-wire transmitter)

0 to 20 mA

4 to 20 mA

"

20 mA

C

You will find the digitized analog
values in Section 5.3.1 in the
current measuring range

R-4L: Resistors

(four-conductor
connection)

48

W

150

W

300

W

600

W

6000

W

A

You will find the digitized analog
values in Section 5.3.1 in the
resistance measuring range

R-3L: Resistors

(three-conductor
connection)

300

W

600

W

6000

W

This manual is related to the following products: