RS 485 Repeater

10-4

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

10.3

RS 485 Repeater in Ungrounded and Grounded

Operation

Grounded or Ungrounded

The RS 485 repeater is ...

grounded, if all other nodes in the segment are also operated with a grounded
potential

ungrounded, if all other nodes in the segment are operated with an ungrounded
potential

Note

The bus segment 1 is grounded if you connect a programming device to the
PG/OP socket of the RS 485 repeater. Ground connection is effected since the
MPI in the programming device is grounded and the PG/OP socket is connected
internally with bus segment 1 in the RS 485 repeater.

Grounded Operation of the RS 485 Repeater

For grounded operation of the RS 485 repeater, you must jump terminals “M” and
“PE” on the top of the RS 485 repeater.

Ungrounded Operation of the RS 485 Repeater

For ungrounded operation of the RS 485 repeater, “M” and “PE” on the top of the
RS 485 repeater must not be interconnected. In addition, the supply voltage of the
RS 485 repeater must be ungrounded.