beautypg.com

Siemens Simatic S7-400 User Manual

Page 34

background image

General Technical Specifications

1-6

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

cuULu requirements on hazardous location on the battery power supply for
CPUs

The power supply to the backup battery of a CPU must be via a non–incendive
plug. The figure below portrays the concept of such connection.

Battery or
Power supply unit

CPU with connector
“ext. batt.”

Cc = Cable capacity
Lc = Cable inductance

Figure 1-1

Power supply to the backup battery

The following conditions apply to the performance characteristics of this
connection:

Voc (no load voltage) = 15V

Vmax = 15V

Isc (short–circuit current )= 50 mA

Imax = 50 mA

Ca = Battery capacity/

Ci = 25 nF maximum

power supply
La= Battery inductance/

Li = 2 mH maximum

power supply

The battery/power supply which supplies the non–ingnitable connection must have
the following values:

Battery/Power supply

CPU iput “Ext. Batt.” incl. cabel

Voc

Vmax (15V)

Isc

Imax (50 mA)

This manual is related to the following products: