Cable Duct and Fan Subassemblies

9-6

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Shielding Clamps

If you do not require the shielding clamps supplied, do not install them in the fan
subassembly.

Technical Specifications

Dimensions, Weights

Dimensions WxHxD (mm)

482.5

Ч

109.5

Ч

235

(

)

Weight

appr. 2000 g

Cable diameter

3 bis 9 mm

Nominal Sizes

Lifespan of the fans

at

40°

C

at

75°

C

70000 h

25000 h

Max. contact load of relay
contacts 1 to 6

Switching voltage

Switching current

24 VDC

200 mA

Voltages, Currents, Potentials

At nominal voltage of

230 VAC

120 VAC

Power consumption

with fan

without fan

17 W

18 W

5 W

4 W

Starting current

0,6 A

1,15 A

Fuses

160 mA

250 mA

!

Warning

Electrical current can lead to personal injury.

If you remove the left cover when installing or removing the fan subassembly, the
terminals on the transformer are accessible briefly.

Remove the voltage from the fan subassembly before you install or remove it.
Disconnect the supply cable before you remove the fan subassembly.

!

Caution

Danger of damage to equipment.

If you mix up the power supply PCB and the monitoring PCB in the fan
subassembly, the fan subassembly may be damaged.

During maintenance of the unit, make sure you do not mix up the power supply
PCB and the monitoring PCB.

Monitoring Function

In the case of a fault (defective fans) the fans are not switched off. Once you have
replaced the defective fan(s), the fault is acknowledged automatically as soon as
the fans have reached the required speed. Any faults that occur are not stored.
When you switch on the fan subassembly, the fans start running. After
approximately 10 s the current status of the fans is indicated via LEDs and relays.