Interface Submodules

13-40

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Connection of Current Sensors as Two-Wire and Four-Wire Transducers

Figures 13-16 and 13-17 show you how to connect current sensors as two-wire
and four-wire transducers to analog input modules.

The 24 V voltage is supplied to the two-wire transducer via a protected output (L1

+

,

L2

+

). The two-wire transducer converts the measured variable to a current of 4 to

20 mA. The range 4 to 20 mA is converted to the required format by a software
driver function.

Four-wire transducers have a separate supply voltage.

Two-wire
transducers

Two-wire
transducers

+24 V

Sensor,
e. g. pressure
gauge

P

P

+
-

+
-

L

+

M

L1

+

M

0-

MI

1+

M

1-

0 V

MI

0-

V

m

V

m

4 to 20
mA

4 to 20
mA

Figure 13-16 Connection of Two-Wire Transducers

+24 V

transducer

Four-wire

+
-

+
-

Sensor,
e. g. pressure
gauge

P

P

L

+

M

MV

0+

M

0-

MV

1+

M

1-

V

CM1

V

CM0

0 V

Figure 13-17 Connection of Four-Wire Transducers