1 parameters of the digital input modules – Siemens Simatic S7-400 User Manual
Page 129
Digital Modules
4-7
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
4.3.1
Parameters of the Digital Input Modules
The parameterized digital input modules use a subset of the parameters and
ranges of values listed in the table below, depending on functionality. Refer to the
section on a particular digital module, starting from Section 4.7, to find out which
subset it is capable of using.
Don’t forget that some digital modules have different time delays after parameter
assignment.
The default settings apply if you have not performed parameter assignment in
STEP 7.
Table 4-6
Parameters of the Digital Input Modules
Parameter
Value Range
Default
2
Parameter
Type
Scope
Enable
•
Diagnostic interrupt
1)
•
Hardware interrupt
1)
Yes/no
Yes/no
No
No
Dynamic
Module
•
Destination CPU for
interrupt
1 to 4
–
Static
Module
Diagnostics
•
Wire break
•
No load voltage
L+/sensor supply
Yes/no
Yes/no
No
No
Static
Channel
Trigger for hardware
interrupt
No
Dynamic
Channel
•
Rising (positive) edge
•
Falling (negative) edge
Yes/no
Yes/no
No
No
Dynamic
Channel
Input delay
0.1 ms (DC)
0.5 ms (DC)
3 ms (DC)
20 ms (DC/AC)
3 (DC)
Static
Channel
Reaction to error
Substitutea value (SV)
Keep last value (KLV)
SV
Dynamic
Module
Substitute“1”
Yes/no
No
Dynamic
Channel
1)
If you use the module in ER-1/ER-2, you must set this parameter to “No” because the interrupt lines are
not available in ER-1/ER-2.
2)
Only in the CC (central controller) is It possible to start up the digital modules with the default settings and
without HWCONFIG support.